Self-regulating heating cables for electric heat tracing

Self-Regulating Heating Cables

Self-regulating heating cables adjust their local heat output with temperature and are used for industrial freeze protection and temperature maintenance. Pro Therm selects suitable constructions around heat loss, temperatures, environment and circuit length. Our manufacturer-independent approach coordinates the cable, connections and controls with your plant.

 

Select a heating cable →

Sample wiring diagrams

 

Examples of direct-switching connections. Click a diagram to enlarge it. Diagram labels are in German.

 

We will be happy to send you further sample wiring diagrams on request.

Request further wiring diagrams →

01

Operating principle

A temperature-responsive heating element between the conductors changes electrical resistance. At lower temperatures heat output increases; at higher temperatures it …

 

A temperature-responsive heating element between the conductors changes electrical resistance. At lower temperatures heat output increases; at higher temperatures it decreases. This characteristic does not remove the need for project-specific design, maximum-temperature checks or appropriate controls.

 

03

Selection criteria

Important criteria include required output at design temperature, maintain and exposure temperatures, supply voltage, maximum circuit length, starting current, jacket …

 

Important criteria include required output at design temperature, maintain and exposure temperatures, supply voltage, maximum circuit length, starting current, jacket material, chemical environment and hazardous-area requirements.

 

The stated output applies to defined test conditions. For a warm process pipe, the output curve at the actual maintenance temperature matters. Maximum operating and exposure temperatures are assessed separately. A freeze protection cable is therefore not automatically suitable for hot cleaning or a much higher process temperature.

 

05

Accessories and connections

A complete system includes compatible power connections, end terminations, tees, junction boxes, fixing materials, sensing and controls. Component compatibility is part …

 

A complete system includes compatible power connections, end terminations, tees, junction boxes, fixing materials, sensing and controls. Component compatibility is part of the system design.

 

07

Read performance curves at the relevant operating point

Nominal outputs of two self-regulating cables are comparable only when reference temperature, supply and test conditions match. A cable with a higher nominal rating may …

 

Nominal outputs of two self-regulating cables are comparable only when reference temperature, supply and test conditions match. A cable with a higher nominal rating may deliver a different output at the required process temperature. Selection therefore compares the performance curve against the calculated heat loss.

 

Product-specific service and ageing conditions and the intended control concept also matter. Self-regulation means local output adjustment. A defined temperature setpoint, alarm function and project-specific overtemperature protection are separate tasks.

 

09

Frequently asked questions

Can self-regulating heat trace overheat? Its temperature-responsive characteristic reduces local heat output, but project-specific checks of exposure temperature, …

 

Can self-regulating heat trace overheat?

Its temperature-responsive characteristic reduces local heat output, but project-specific checks of exposure temperature, hazardous-area requirements and controls are still necessary.

 

Can self-regulating cable be cut to length?

Many systems can be cut to length within their product rules, but maximum circuit lengths and termination requirements for the specific cable must be followed.

 

Does self-regulating heat trace need a thermostat?

It depends on the application, energy-efficiency target, process requirements and product specification. Temperature control is often beneficial and can be required.

 

How should I compare two nominal outputs?

Use the same reference conditions. The relevant curve is the output at the required maintain temperature and supply, alongside cold start, maximum circuit length and product service limits.

 

11

Related topics

Freeze protection → Temperature maintenance → Controls and monitoring → Hazardous-area heat tracing → Pipe heat tracing → Heat loss and insulation → Resistance heating …

02

Typical applications

Self-regulating cables are widely used for pipe freeze protection, process temperature maintenance, tank and vessel connections, instrument lines and other industrial …

 

Self-regulating cables are widely used for pipe freeze protection, process temperature maintenance, tank and vessel connections, instrument lines and other industrial applications.

 

04

Hazardous areas

Suitable cable variants and approved system components must be selected for hazardous locations. Certificates and permitted operating conditions must be checked for the …

 

Suitable cable variants and approved system components must be selected for hazardous locations. Certificates and permitted operating conditions must be checked for the actual product.

 

06

Cold start and maximum circuit length

Electrical design takes the lowest start-up temperature into account. A cold self-regulating cable may initially draw more current than it does during normal operation. …

 

Electrical design takes the lowest start-up temperature into account. A cold self-regulating cable may initially draw more current than it does during normal operation. Maximum circuit length is therefore taken from product-specific tables for supply voltage, start-up temperature and the protective device. All connected branches contribute to the total. A nominal rating such as 10, 20 or 30 W/m alone is insufficient to determine circuit protection or maximum length.

 

Agree the brand and budget with us: our engineering is independent of a single manufacturer. Depending on suitability, we select Pro Therm own-brand materials or products from eltherm, BARTEC, RAYCHEM/Chemelex and Thermon. Tell us your preferred construction and budget range.

 

08

Standards and technical basis

Our knowledge section explains how the standards relate to the heating task, product selection and project design. Open the standards overview →

Our knowledge section explains how the standards relate to the heating task, product selection and project design.

Open the standards overview →

 

10

Select a self-regulating cable

Provide pipe and heating lengths, voltage, lowest start temperature, target temperature and maximum exposure. Use the heating cable enquiry form to assemble quantities …

Provide pipe and heating lengths, voltage, lowest start temperature, target temperature and maximum exposure. Use the heating cable enquiry form to assemble quantities and requirements; final selection follows technical assessment.

Select a heating cable →

 

12

References & projects

Explore our project reports for electric heat tracing and frost heave protection. View references & projects →

Explore our project reports for electric heat tracing and frost heave protection.

View references & projects →

​

​

​

​

​

​

​

​